CULLIN AFRICA - COMPANY PROFILE
Cullin Africa, a Black South African Women owned company, has grown to become one of the biggest High Voltage overhead line
material suppliers in Southern Africa, since its inception in 1998.
Our major customers include Eskom, Telkom, Transnet, Nampower, municipalities and most utilities in
Southern Africa.. We supply good quality local and overseas manufactured products. The company has
the support and technical backup from all major Approved Manufacturers, Suppliers and Importers, for
all the related products that we supply. Cullin Africa is the sole agent for SEDIVER Insulators, in the
South Africa and Sub-Saharan markets.
Although every effort has been made to eliminate errors from this catalogue, the information provided
should be used for specification purposes. Please contact Cullin Africa cc directly to confirm
any critical data. Cullin reserves the right to alter any data without prior warning.
Internet
Please visit our Home Page, www.cullin.co.za, on the Internet for regular news on Cullin Africa, our
products, services and people. You can even cut your communication costs by sending your enquiries and
orders via e-mail. Our e-mail address is [email protected]
Other Products
Cullin Africa currently makes a wide range of different products,
many of which are custom designed. Obviously we cannot show our
full products in these pages so if you cannot find what you are looking
for, please call us - we may well have what you want. Be it hollow
porcelains, transformer bushings or support insulators, we cover a
broad range.
Standards
Standards and specifications are compiled at international level by experts in their
respective fields as a guide to aid the manufacturer, the designer and the user.
Specifications ensure standardisation of technical and performance requirements on a
global scale. At Cullin our products are manufactured in accordance with and in
compliance to the various relevant specifications, namely: A.N.S.I. (American
International Electrotechnical Commission), D.I.N. & V.D.E. (German Electrotechnical
Commission) and S.A.B.S. (South African Bureau of Standards). All the S.A.B.S.
standards are based on the relevant IEC Standards, and tests are done at the South
African High Voltage Test Facility (N.E.T.F.A.), which is Kema accredited.
Cullin can also work to other standards systems as and when required. Please contact
us for further information.
CURRENT PRODUCT / COMMODITY RANGES MADE IN PORCELAIN
Electric insulators and Applications.
Low Voltage: (L.V.) < 1kV.
- Telephone Insulators - Single groove / double groove.
- L.V. Pin Insulators.
- Shackle Insulators.
- Reel Insulators.
- Busbar Insulators - < 1kV
High Voltage: (H.V.) > 1kV
Line Post
IEC 383/SABS177
11kV To 66kV
Metal capped units & capless units
4kN to 12.5kN Cantilever Strength
135kV BIL to ± 300kV BIL
Longrods
IEC 433
11kv To 66kV
Fixtures: socket / clevis / tongue
Configuration: Inline or twisted
40kN to 70kN - tensile strength
Railway Traction
AC/DC applications
3kV - 25kV - 50kV
Fixtures: strut / tension
Pantograph Insulators
(Railway)
Various
Support Insulators (Post)
Station Class
6.6kV To 400kV - IEC & ANSI
specifications
Normal / medium / exceptional creepage
Normal / medium / high cantilever
strength 4kN to 20kN
Fixtures: 76mm PCD to 254mm PCD
Fuse Insulators
Drop-out - 22kV to 33kV
Rocker Types - 11kV to 33kV
Surge Arresters
(Station Class)
11kV to 400kV
Normal / medium / high creepage
Current/Volt Transformer
Bushings
(Oil filled)
11kV to 275kV* (Glued*)
Normal / medium /High creepage
Condenser Bushings
(Power Transformers)
22kV to 132kV
Disconnecter Chambers
SF6 - Circuit Breakers
Oil - Circuit Breakers
Various
Distribution Transformer
Bushings
1.1kV to 36kV (up to 2500 AMP)
S.A.B.S. & DIN specifications
Through Wall Bushings
11kV to 22kV
Cable Box Bushings
11kV to 33kV
Resistance Insulators
Various (Railways)
Precipitator Insulators
Barrel type and through wall type
Security Fence Insulators
Various
Cable end Bushings
Various
Specials
Various
Oil filled Bushings
Drive insulators (Rapper)
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
DIMENSIONAL LIMITATIONS OF INSULATORS
1. One-Piece Porcelain
1.1
Hollow Insulators
Maximum Height
Maximum Shed Diameter
1.2
1.3
1.4
2
1700mm
650mm
Height
Minimum Wall Thickness
Minimum Bore Diameter
671-1700mm
25mm
120mm
Height
Minimum Wall Thickness
Minimum Bore Diameter
Less than 671mm
10mm
38mm
Line Post Insulators
Height - Maximum
- Minimum
930mm
180mm
Maximum Core Diameter
140mm
Maximum Shed Overhang
75mm
Stattion Post Insulators (one - piece)
Height - Maximum
- Minimum
1640mm
120mm
Maximum Core Diameter
150mm
Maximum Shed Overhang
90mm
Stattion Post Insulators (two - piece)
Height - Maximum
3150mm
Maximum Cantilever
6kN (at 3150mm)
Maximum Core Diameter
150mm
Maximum Shed Overhang
75mm
Multi-section Porcelain - Hollows (epoxy bonding)
Height - Maximum
3800mm
Maximum Shed Diameter
650mm
Minimum Wall Thickness
30mm
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 01
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP321-01 EP322-00 EP322-03 EP323-00 EP323-01 EP323-04
IEC Designation
Nominal Voltage
C4-60
C10-95
C4-95
C4-125
C4-125
C4-125
kV
6.6
12
11
16
16
16
Overall Length
L
mm
190
255
255
305
305
305
Largest Shed Dia.
D
mm
156
190
170
190
190
170
2
3
3
4
4
4
mm
190
380
380
460
500
500
Number of Sheds
Top
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
104
130
104
130
130
130
Pitch Circle Diameter
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
104
130
104
130
130
130
Cantilever Strength
kN
4
10
4
4
4
4
Torsional Strength
Nm
600
2900
1500
800
800
800
Tensile Strength
kN
50
---
50
---
---
---
Compression Strength
kN
160
---
160
---
---
---
Dry Arcing Distance
mm
95
172
152
---
---
---
Power Frequency Flashover Dry
kV
64
95
86
---
---
---
Power Frequency Flashover Wet
kV
52
50
60
---
---
---
Power Frequency Withstand Dry
kV
57
90
76
---
---
---
Power Frequency Withstand Wet
kV
37
45
49
50
50
50
Impulse Withstand Voltage (BIL)
kV
104
150
146
125
125
125
Impulse Flashover Positive
kV
111
155
151
---
---
---
Impulse Flashover Negative
kV
134
245
215
---
---
---
Weight
kg
5.1
10.5
8
---
---
7.6
Packed Weight
kg
6
11.2
8.5
---
---
8.5
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 02
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP568-00 EP568-01 EP312-00 EP312-01 EP312-02 EP1064-00
IEC Designation
Nominal Voltage
C4-150
C4-150
C10-150
C10-150*
C10-150
C4-150
kV
22
22
22
22
22
22
Overall Length
L
mm
355
355
355
355
355
355
Largest Shed Dia.
D
mm
184
184
205
205
205
206
5
5
5
5
5
6
mm
680
680
665
665
665
790
Number of Sheds
Top
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
116
116
131
131
131
116
Pitch Circle Diameter
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
116
116
131
131
131
116
Cantilever Strength
kN
4
4
10
10
10
4
Torsional Strength
Nm
2000
2000
2000
2000
2000
2000
Tensile Strength
kN
50
50
50
50
50
50
Compression Strength
kN
160
160
160
160
160
160
Dry Arcing Distance
mm
250
250
250
250
250
277
Power Frequency Flashover Dry
kV
98
98
110
110
110
118
Power Frequency Flashover Wet
kV
81
81
70
70
70
86
Power Frequency Withstand Dry
kV
93
93
90
90
90
108
Power Frequency Withstand Wet
kV
64
64
60
60
60
74
Impulse Withstand Voltage (BIL)
kV
181
150
150
150
150
192
Impulse Flashover Positive
kV
190
190
190
190
190
203
Impulse Flashover Negative
kV
304
304
300
300
300
270
Weight
kg
11.5
11.5
14
14
14
---
Packed Weight
kg
12.6
12.6
15.5
15.5
15.5
---
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
* For torsional use
Brown
Blue
Brown
Brown
Blue
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 03
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP873-00 EP874-00 EP313-00 EP313-01 EP313-02 EP313-04
IEC Designation
Nominal Voltage
C4-170
C4-170
C4-200
C4-200
C4-200*
C6-200
kV
27
27
33
33
33
33
Overall Length
L
mm
445
445
475
475
475
475
Largest Shed Dia.
D
mm
195
175
216
216
216
216
8
8
8
8
8
8
mm
900
750
1100
1100
1100
1100
Number of Sheds
Top
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
131
131
131
131
131
131
Pitch Circle Diameter
d1
mm
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
131
131
131
131
131
131
Cantilever Strength
kN
4
4
4
4
4
6
Torsional Strength
Nm
---
---
1500
1500
1500
1800
Tensile Strength
kN
---
---
50
50
50
50
Compression Strength
kN
---
---
160
160
160
160
Dry Arcing Distance
mm
---
---
356
356
356
356
Power Frequency Flashover Dry
kV
130
130
150
150
150
150
Power Frequency Flashover Wet
kV
80
80
100
100
100
100
Power Frequency Withstand Dry
kV
120
120
120
120
120
120
Power Frequency Withstand Wet
kV
70
70
90
90
90
90
Impulse Withstand Voltage (BIL)
kV
170
170
200
200
200
200
Impulse Flashover Positive
kV
200
200
230
230
230
230
Impulse Flashover Negative
kV
275
275
300
300
300
300
Weight
kg
---
---
22.3
22.3
22.3
22.3
Packed Weight
kg
---
---
24.4
24.4
24.4
24.4
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
* For torsional use
Brown
Brown
Brown
Blue
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 04
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP814-00 EP313-05 EP529-00 EP314-00 EP314-01 EP314-05
IEC Designation
Nominal Voltage
C4-200
C6-200*
C10-200
C6-250
C6-250
C4-250
kV
33
33
33
44
44
44
Overall Length
L
mm
475
475
519
560
560
560
Largest Shed Dia.
D
mm
194
216
235
216
216
194
8
8
8
10
10
10
mm
1100
1100
1000
1300
1300
1300
Number of Sheds
Top
d1
mm
76(M12)
76(M12)
127(M16)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
116
131
164
131
131
116
Pitch Circle Diameter
d1
mm
76(M12)
76(M12)
127(M16)
76(M12)
76(M12)
76(M12)
Flange Diameter
d
mm
116
131
164
131
131
116
Cantilever Strength
kN
4
6
10
6
6
4
Torsional Strength
Nm
1500
1800
1500
2000
2000
2000
Tensile Strength
kN
50
50
50
50
50
50
Compression Strength
kN
160
160
160
160
160
160
Dry Arcing Distance
mm
356
356
356
450
450
450
Power Frequency Flashover Dry
kV
145
150
140
170
170
170
Power Frequency Flashover Wet
kV
129
100
100
125
125
125
Power Frequency Withstand Dry
kV
135
120
120
150
150
150
Power Frequency Withstand Wet
kV
107
90
80
105
105
105
Impulse Withstand Voltage (BIL)
kV
239
200
200
250
250
250
Impulse Flashover Positive
kV
254
230
220
275
275
275
Impulse Flashover Negative
kV
375
300
300
350
350
350
Weight
kg
15.5
22.3
30
25.9
25.9
22
Packed Weight
kg
17.5
24.4
32
28
28
24
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
* For torsional use
Brown
Brown
Brown
Brown
Blue
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 05
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP716-00 EP1067-00 EP1132-00 EP315-00 EP315-01 EP315-02
IEC Designation
C10-250
C4-250
C4-250
C4-325
C4-325
C4-325
kV
44
44
44
66
66
66
Nominal Voltage
Overall Length
L
mm
600
550
560
770
770
770
Largest Shed Dia.
D
mm
235
216
209
200
200
200
10
10
10
15
15
15
mm
1300
1300
1500
1700
1700
1700
Number of Sheds
Top
d1
mm
127(M16)
76(M12)
76(M12)
127(M16)
76(M12)
127(M16)
Flange Diameter
d
mm
164
131
116
159
132
159
Pitch Circle Diameter
d1
mm
127(M16)
76(M12)
76(M12)
127(M16)
76(M12)
127(M16)
Flange Diameter
d
mm
164
131
116
159
132
159
Cantilever Strength
kN
10
4
4
4
4
4
Torsional Strength
Nm
2000
2000
2000
3000
3000
3000
Tensile Strength
kN
50
50
50
60
60
60
Compression Strength
kN
160
160
160
200
200
200
Dry Arcing Distance
mm
450
450
450
640
640
640
Power Frequency Flashover Dry
kV
170
170
170
225
225
225
Power Frequency Flashover Wet
kV
125
125
125
175
175
175
Power Frequency Withstand Dry
kV
150
150
150
200
200
200
Power Frequency Withstand Wet
kV
105
105
105
170
170
170
Impulse Withstand Voltage (BIL)
kV
250
250
250
325
325
325
Impulse Flashover Positive
kV
275
275
275
350
350
350
Impulse Flashover Negative
kV
350
350
350
500
500
500
Weight
kg
40
25.9
---
31.9
31.9
31.9
Packed Weight
kg
42.5
28
---
34
34
34
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
* For torsional use
Brown
Brown
Brown
Brown
Brown
Blue
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 06
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP888-00 EP888-01 EP1148-00 EP902-00 EP902-01 EP560-00
IEC Designation
Nominal Voltage
C4-325
C4-325
C4-325
C6-325
C6-325
C8-325
kV
66
66
66
66
66
66
Overall Length
L
mm
770
770
770
770
770
770
Largest Shed Dia.
D
mm
220
220
260
220
220
220
16
16
8(Big)
16
16
15
mm
2000
2000
2400
2000
2000
1650
76(M12)
127(M16)
132
164
76(M12)
127(M16)
Number of Sheds
Top
d1
mm
127(M16)
76(M12)
Flange Diameter
d
mm
159
132
Pitch Circle Diameter
d1
mm
127(M16)
76(M12)
Flange Diameter
d
mm
159
132
159
159
132
164
Cantilever Strength
kN
4
4
4
6
6
8
Torsional Strength
Nm
3000
3000
3000
3000
3000
3000
Tensile Strength
kN
60
60
60
60
60
100
Compression Strength
kN
200
200
200
200
200
200
Dry Arcing Distance
mm
640
640
640
640
640
640
Power Frequency Flashover Dry
kV
225
225
225
225
225
225
Power Frequency Flashover Wet
kV
175
175
175
175
175
175
Power Frequency Withstand Dry
kV
200
200
200
200
200
200
Power Frequency Withstand Wet
kV
170
170
170
170
170
170
Impulse Withstand Voltage (BIL)
kV
325
325
325
325
325
325
Impulse Flashover Positive
kV
350
350
350
350
350
350
Impulse Flashover Negative
kV
500
500
500
500
500
500
Weight
kg
35.8
35.8
---
35.8
35.8
43
Packed Weight
kg
37.8
37.8
---
37.8
37.8
45.5
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
* For torsional use
127(M16) 127(M16)
159
159
127(M16) 127(M16)
Brown
Brown
Brown
Brown
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 07
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP316-00 EP916-00 EP316-01 EP316-05 EP317-00 EP317-01
IEC Designation
Nominal Voltage
C4-380
C4-380
C6-380
C4-380
C4-450
C6-450
kV
88
88
88
88
88-100
88-100
Overall Length
L
mm
870
870
870
870
1020
1020
Largest Shed Dia.
D
mm
236
262
236
210
240
240
16
16
16
16
18
18
2000
2500
2000
2000
2500
2500
Number of Sheds
Nominal Creepage Distance
Top
d1
mm
Flange Diameter
d
mm
Pitch Circle Diameter
d1
mm
Flange Diameter
d
mm
164
164
164
159
164
164
Cantilever Strength
kN
4
4
6
4
4
6
Torsional Strength
Nm
4000
4000
4000
4000
2500
2500
Tensile Strength
kN
100
100
100
100
100
100
Compression Strength
kN
300
300
300
300
300
300
Dry Arcing Distance
mm
700
700
700
700
875
875
Power Frequency Flashover Dry
kV
270
270
270
270
330
330
Power Frequency Flashover Wet
kV
200
200
200
200
270
270
Power Frequency Withstand Dry
kV
225
225
225
225
320
320
Power Frequency Withstand Wet
kV
150
150
150
150
240
240
Impulse Withstand Voltage (BIL)
kV
380
380
380
380
450
450
Impulse Flashover Positive
kV
400
400
400
400
575
575
Impulse Flashover Negative
kV
550
550
550
550
825
825
Weight
kg
51.6
57.8
51.6
46
54.9
54.9
Packed Weight
kg
55
61.2
55
49
64.3
64.3
Dimensions
Pitch Circle Diameter
Bottom
mm
Colour
Packing Description
* For torsional use
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
164
164
164
159
164
164
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
Brown
Brown
Brown
Brown
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 08
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP318-00 EP318-01 EP318-10 EP557-00 EP557-05 EP318-02
IEC Designation
Nominal Voltage
C4-550
C6-550
C4-550
C4-550
C4-550
C8-550
kV
132
132
132
132
132
132
Overall Length
L
mm
1220
1220
1220
1220
1220
1220
Largest Shed Dia.
D
mm
234
234
218
235
210
234
22
22
22
29
29
22
3050
3050
3130
3625
3625
3050
Number of Sheds
Nominal Creepage Distance
Top
d1
mm
Flange Diameter
d
mm
Pitch Circle Diameter
d1
mm
Flange Diameter
d
mm
164
164
159
164
159
164
Cantilever Strength
kN
4
6
4
4
4
8
Torsional Strength
Nm
3000
3000
3000
3000
3000
3000
Tensile Strength
kN
100
100
100
100
100
100
Compression Strength
kN
300
300
300
300
300
300
Dry Arcing Distance
mm
1050
1050
1050
1050
1050
1050
Power Frequency Flashover Dry
kV
531
531
369
520
348
520
Power Frequency Flashover Wet
kV
288
288
331
280
323
280
Power Frequency Withstand Dry
kV
523
523
353
500
335
500
Power Frequency Withstand Wet
kV
258
258
297
230
306
230
Impulse Withstand Voltage (BIL)
kV
756
756
634
550
683
550
Impulse Flashover Positive
kV
777
777
667
700
716
700
Impulse Flashover Negative
kV
1036
1036
828
950
788
950
Weight
kg
70.3
70.3
47.2
70.9
57.5
70.3
Packed Weight
kg
79.7
79.7
51
79.5
60
79.7
Dimensions
Pitch Circle Diameter
Bottom
mm
Colour
Packing Description
* For torsional use
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
164
164
159
164
159
164
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
Brown
Blue
Brown
Brown
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 09
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP1057-00 EP310-00 EP310-02 EP310-04 EP310-01 EP1056-00
IEC Designation
Nominal Voltage
C4-550
C4-650
C4-650
C4-650
C6-650
C4-650
kV
132
132
132
132
132
132
Overall Length
L
mm
1220
1500
1500
1500
1500
1500
Largest Shed Dia.
D
mm
264
234
234
214
234
235
15(Big)
28
28
28
28
18(Big)
4700
3750
3750
3930
3750
4700
Number of Sheds
Nominal Creepage Distance
Top
d1
mm
Flange Diameter
d
mm
Pitch Circle Diameter
d1
mm
Flange Diameter
d
mm
159
164
164
159
164
159
Cantilever Strength
kN
4
4
4
4
6
4
Torsional Strength
Nm
3000
3000
3000
3000
3000
3000
Tensile Strength
kN
100
100
100
100
100
100
Compression Strength
kN
300
300
300
300
300
300
Dry Arcing Distance
mm
1130
1350
1350
1350
1350
1375
Power Frequency Flashover Dry
kV
383
464
464
464
464
499
Power Frequency Flashover Wet
kV
350
379
379
379
379
426
Power Frequency Withstand Dry
kV
366
460
460
460
460
444
Power Frequency Withstand Wet
kV
299
340
340
340
340
341
Impulse Withstand Voltage (BIL)
kV
666
750
750
750
750
819
Impulse Flashover Positive
kV
687
770
770
770
770
840
Impulse Flashover Negative
kV
886
948
948
885
948
1044
Weight
kg
---
82.4
82.4
62.8
82.4
90.5
Packed Weight
kg
---
89.5
89.5
69
89.5
96.8
Dimensions
Pitch Circle Diameter
Bottom
mm
Colour
Packing Description
* For torsional use
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
159
164
164
159
164
159
127(M16) 127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
Brown
Brown
Blue
Brown
Brown
Brown
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
1 - 10
STATION POST INSULATORS
METALWARE:
D
MATERIAL: SG42/M.C.I.
-TO SABS 963/1970
L
- TO BS 2789/1973-420/12
HOT DIP GALVANIZED
- TO SABS 763
- TO BS 729 OR ISO 1461
d1
d1
d
d
4 Tapped Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
PR0049
IEC Designation
C4-750
Nominal Voltage
kV
170
Overall Length
L
mm
1700
Largest Shed Dia.
D
mm
250
Number of Sheds
41
Nominal Creepage Distance
mm
5800
mm
---
Flange Diameter
d
mm
---
Pitch Circle Diameter
d1
mm
---
Flange Diameter
d
mm
---
Cantilever Strength
kN
4
Torsional Strength
Nm
---
Tensile Strength
kN
---
Compression Strength
kN
---
Dry Arcing Distance
mm
---
Power Frequency Flashover Dry
kV
---
Power Frequency Flashover Wet
kV
---
Power Frequency Withstand Dry
kV
---
Power Frequency Withstand Wet
kV
---
Impulse Withstand Voltage (BIL)
kV
750
Impulse Flashover Positive
kV
---
Impulse Flashover Negative
kV
---
Weight
kg
---
Packed Weight
kg
---
Bottom
Top
d1
Dimensions
Pitch Circle Diameter
Colour
Packing Description
* For torsional use
Brown
Wire bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
2 - 01
STATION POST INSULATORS
METALWARE:
4 Tapped
Holes
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
4 Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP845-00 EP701-00 EP785-00
IEC Designation
Nominal Voltage
C6-750
C4-1050
C4-1050
kV
185
275
275
Overall Length
L
mm
1700
2300
2300
Largest Shed Dia.
D
mm
235
227
277
mm
4250
6000
6900
Nominal Creepage Distance
mm
Flange Diameter
d
mm
164
164
164
Pitch Circle Diameter
d1
mm
127(M16)
225(18)
225(18)
Flange Diameter
d
mm
164
260
260
Cantilever Strength
kN
6
4
4
Torsional Strength
Nm
3000
3000
3000
Tensile Strength
kN
---
---
---
Compression Strength
kN
---
---
---
Dry Arcing Distance
mm
---
2270
2095
Power Frequency Flashover Dry
kV
500
773
703
Power Frequency Flashover Wet
kV
335
614
608
Power Frequency Withstand Dry
kV
460
741
657
Power Frequency Withstand Wet
kV
325
531
559
Impulse Withstand Voltage (BIL)
kV
750
1301
1249
Impulse Flashover Positive
kV
800
1339
1302
Impulse Flashover Negative
kV
900
1482
1514
Weight
kg
---
207.3
175.3
Packed Weight
kg
---
214.9
182.9
Bottom
Top
d1
Dimensions
Pitch Circle Diameter
Colour
Packing Description
127(M16) 127(M16) 127(M16)
Brown
Brown
Brown
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
2 - 02
STATION POST INSULATORS
METALWARE:
4 Tapped
Holes
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
8 Holes
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP822-00 EP824-00 EP700-00 EP821-00
IEC Designation
Nominal Voltage
C8-1050
C6-1300
C6-1425
C6-1425
kV
275
350
400
400
Overall Length
L
mm
2300
2900
3150
3150
Largest Shed Dia.
D
mm
250
250
250
290
mm
6000
7500
9300
10500
Top
d1
mm
Flange Diameter
d
mm
164
164
164
164
Pitch Circle Diameter
d1
mm
254(18)
254(18)
254(18)
254(18)
Flange Diameter
d
mm
292
292
292
292
Cantilever Strength
kN
8
6
6
6
Torsional Strength
Nm
4000
3000
3000
3000
Tensile Strength
kN
---
---
---
---
Compression Strength
kN
---
---
---
---
Dry Arcing Distance
mm
---
---
3200
2888
Power Frequency Flashover Dry
kV
721
650
1021
897
Power Frequency Flashover Wet
kV
586
625
905
761
Power Frequency Withstand Dry
kV
680
620
978
831
Power Frequency Withstand Wet
kV
514
600
729
700
Impulse Withstand Voltage (BIL)
kV
1214
1300
1816
1731
Impulse Flashover Positive
kV
1247
1400
1860
1804
Impulse Flashover Negative
kV
1352
1500
2006
1985
Weight
kg
193.5
---
245.4
284
Packed Weight
kg
201.1
---
253
292
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
127(M16) 127(M16) 127(M16) 127(M16)
Brown
Brown
Brown
Brown
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
2 - 03
INVERTED STATION POST INSULATORS
METALWARE:
4 Tapped
Holes
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
8 Holes (254)
4 Holes (225)
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP920-00 EP913-00 EP850-00 EP928-00 EP991-00
IEC Designation
Nominal Voltage
C4-950
C4-1050
C4-1050
C8-1050
C6-1425
kV
275
275
275
275
400
Overall Length
L
mm
2100
2300
2300
2300
3150
Largest Shed Dia.
D
mm
227
277
227
250
250
mm
5350
6900
6000
6000
8600
Top
d1
mm
225(18)
225(18)
225(18)
254(18)
254(18)
Flange Diameter
d
mm
260
260
260
292
292
Pitch Circle Diameter
d1
mm
Flange Diameter
d
mm
164
164
164
164
164
Cantilever Strength
kN
4
4
4
8
6
Torsional Strength
Nm
3000
3000
3000
4000
3000
Tensile Strength
kN
---
---
---
---
---
Compression Strength
kN
---
---
---
---
---
Dry Arcing Distance
mm
---
---
---
---
---
Power Frequency Flashover Dry
kV
600
700
550
700
750
Power Frequency Flashover Wet
kV
440
550
480
550
680
Power Frequency Withstand Dry
kV
570
650
520
650
700
Power Frequency Withstand Wet
kV
400
460
460
460
630
Impulse Withstand Voltage (BIL)
kV
950
1050
1050
1050
1425
Impulse Flashover Positive
kV
1000
1250
1100
1250
1500
Impulse Flashover Negative
kV
1100
1350
1200
1350
1600
Weight
kg
---
175.3
207.3
193.5
245.4
Packed Weight
kg
---
182.9
214.9
201.1
253
Dimensions
Pitch Circle Diameter
Bottom
Nominal Creepage Distance
Colour
Packing Description
127(M16) 127(M16) 127(M16) 127(M16) 127(M16)
Brown
Brown
Brown
Brown
Brown
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Wraggle
Bars Pallets
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
3 - 01
CAPPED LINE POST INSULATORS
d1
F-Neck
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
L
METALWARE:
D
Counter-Sunk Ratchet Lock
d
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP461-00 EP800-00 EP477-00 EP1045-00 EP356-01 EP303-01
kV
11
11
11
11
22
22
Overall Length
L mm
205
212
206
222
295
289
Largest Shed Dia.
D mm
198
167
160
165
145
207
2
3
3
4
4
4
mm
250
388
300
405
400
546
Bottom Fixing Diameter
d mm
M20
M20
M20
M20
M20
M20
Top Fixing Diameter
d1 mm
73
73
73
73
73
73
Top Groove Radius
R mm
25
20
12.5
25
12.5
25
Cantilever Strength
kN
12.5
10
7
12.5
4
12.5
Dry Arcing Distance
mm
---
210
160
170
218
234
Power Frequency Flashover Dry
kV
---
81
70
79.7
97
111
Power Frequency Flashover Wet
kV
---
46
40
43.7
65
63
Power Frequency Withstand Dry
kV
---
72
63
75.1
91
102
Power Frequency Withstand Wet
kV
---
41
35
38
57
55
Impulse Withstand Voltage (BIL)
kV
---
128
100
95
150
150
Impulse Flashover Positive
kV
---
134
110
142.8
164
170
Impulse Flashover Negative
kV
---
213
183
218.2
263
300
Weight
kg
7.6
5
5
7.8
6.4
11.5
Packed Weight
kg
8.5
5.6
5.6
8.3
7
12.5
Number of Sheds
Nominal Creepage Distance
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
3 - 02
CAPPED LINE POST INSULATORS
d1
F-Neck
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
L
METALWARE:
D
Counter-Sunk Ratchet Lock
d
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP303-00 EP333-00 EP306-03 EP801-00 EP802-00 EP802-01
kV
22
22
33
33
33
33
Overall Length
L mm
289
350
390
334
427
427
Largest Shed Dia.
D mm
207
207
208
180
180
180
4
5
6
7
10
10
mm
546
725
866
813
1100
1100
Bottom Fixing Diameter
d mm
M20
M20
M20
M20
M20
M22
Top Fixing Diameter
d1 mm
73
73
73
73
73
73
Top Groove Radius
R mm
25
25
25
20
20
20
Cantilever Strength
kN
12.5
12.5
16
10
10
10
Dry Arcing Distance
mm
234
300
351
335
425
425
Power Frequency Flashover Dry
kV
111
137
148
123
140
140
Power Frequency Flashover Wet
kV
63
92
88
87
91
91
Power Frequency Withstand Dry
kV
102
125
139
115
124
124
Power Frequency Withstand Wet
kV
55
77
71
72
82
82
Impulse Withstand Voltage (BIL)
kV
150
214
246
192
245
245
Impulse Flashover Positive
kV
170
225
258
197
255
255
Impulse Flashover Negative
kV
300
378
424
370
414
414
Weight
kg
11.5
13
15.5
11.5
14.4
14.4
Packed Weight
kg
12.5
14.5
16.6
12.2
14.9
14.9
Number of Sheds
Nominal Creepage Distance
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
3 - 03
CAPPED LINE POST INSULATORS
d1
F-Neck
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
D
Counter-Sunk Ratchet Lock
L
METALWARE:
d
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP480-00 EP1047-00 EP1078-00
kV
33
33
33
Overall Length
L mm
373
438
533
Largest Shed Dia.
D mm
170
180
242
7
10
10
mm
786
1050
1319
Bottom Fixing Diameter
d mm
M20
M20
M22
Top Fixing Diameter
d1 mm
73
73
76
Top Groove Radius
R mm
25
25
25
Cantilever Strength
kN
4
12.5
12.5
Dry Arcing Distance
mm
320
390
480
Power Frequency Flashover Dry
kV
127
157
170
Power Frequency Flashover Wet
kV
74
106
142
Power Frequency Withstand Dry
kV
131
145.9
164
Power Frequency Withstand Wet
kV
87
87.6
119
Impulse Withstand Voltage (BIL)
kV
205
247
288
Impulse Flashover Positive
kV
209
258.4
297
Impulse Flashover Negative
kV
346
413.7
536
Weight
kg
10.5
16
---
Packed Weight
kg
11
16.8
---
Number of Sheds
Nominal Creepage Distance
Colour
Packing Description
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
3 - 04
CAPPED LINE POST INSULATORS
Clamp
Top
F-Neck
Square
Pole
Horizontal Mounting
METALWARE:
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
Counter-Sunk
Ratchet Lock
Clamp
Top
Round
Pole
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP295-00 EP295-01 EP295-02 EP296-00 EP296-01 EP296-02
kV
66
66
66
66
66
66
Overall Length
L mm
700
691
691
744
744
744
Largest Shed Dia.
D mm
264
264
264
264
264
264
14
14
14
14
14
14
Number of Sheds
Nominal Creepage Distance
mm
1950
1950
1950
1950
1950
1950
Horizontal
Square
M22
Horizontal
Round
Horizontal
Square
Bottom Fixing Diameter
d mm
M22
Horizontal
Square
Top Fixing Diameter
d1 mm
73
73
73
Clamp
Clamp
Clamp
Top Groove Radius
R mm
25
25
25
N/A
N/A
N/A
Cantilever Strength
kN
12.5
12.5
12.5
12.5
12.5
12.5
Dry Arcing Distance
mm
640
640
640
640
640
640
Power Frequency Flashover Dry
kV
241
241
241
241
241
241
Power Frequency Flashover Wet
kV
180
180
180
180
180
180
Power Frequency Withstand Dry
kV
228
228
228
228
228
228
Power Frequency Withstand Wet
kV
158
158
158
158
158
158
Impulse Withstand Voltage (BIL)
kV
350
350
350
350
350
350
Impulse Flashover Positive
kV
379
379
379
379
379
379
Impulse Flashover Negative
kV
621
621
621
621
621
621
Weight
kg
46
49
49
---
---
---
Packed Weight
kg
47.2
50.2
50.2
---
---
---
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
4 - 01
LINE POST INSULATORS (CAPLESS)
F-Neck
METALWARE: Steel Insert
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP476-00 EP474-00 EP472-03 EP967-00 EP965-00 EP813-00
kV
11
22
22
22
22
33
Overall Length
L mm
205
236.9
290
322
322
363
Largest Shed Dia.
D mm
150
150
152
156
167
247
3
6
7
8
8
4(Big)
330
500
630
750
750
1115
Number of Sheds
Nominal Creepage Distance
mm
Bottom Fixing Diameter
d mm
M20
Oversize
M20
Oversize
M20
Oversize
M20
Oversize
M20
Oversize
M20
Oversize
Top Fixing Diameter
d1 mm
73
73
73
73
73
115
Top Groove Radius
R mm
20
20
20
20
20
25
Cantilever Strength
kN
10
4
4
4
10
16
Dry Arcing Distance
mm
193
230
290
325
325
405
Power Frequency Flashover Dry
kV
76.7
92
124
109
111
144
Power Frequency Flashover Wet
kV
45.4
71
84
86
85
111
Power Frequency Withstand Dry
kV
74.2
82
121
106
106
136
Power Frequency Withstand Wet
kV
38.5
61
76
72
69
81
Impulse Withstand Voltage (BIL)
kV
125.7
135
183
184
186
220
Impulse Flashover Positive
kV
132.1
139
187
191
193
233
Impulse Flashover Negative
kV
238.3
302
362
343
344
438
Weight
kg
6
5.7
7.1
8.6
10.2
20
Packed Weight
kg
6.5
6.3
7.8
9.3
11
21
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Colour
Packing Description (see Packing Pages)
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
4 - 02
LINE POST INSULATORS (CAPLESS)
F-Neck
METALWARE: Steel Insert
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
EP1046-00 EP1054-00 EP1088-00
kV
33
33
33
Overall Length
L mm
364
401
369
Largest Shed Dia.
D mm
180
210
209
10
10
10
900
1120
1120
Number of Sheds
Nominal Creepage Distance
mm
Bottom Fixing Diameter
d mm
M20
Oversize
M20
Oversize
M20
Oversize
Top Fixing Diameter
d1 mm
73
73
73
Top Groove Radius
R mm
20
20
20
Cantilever Strength
kN
6
10
4
Dry Arcing Distance
mm
389
390
415
Power Frequency Flashover Dry
kV
161
105.7
137.1
Power Frequency Flashover Wet
kV
123
86.4
101.1
Power Frequency Withstand Dry
kV
146
96
131.1
Power Frequency Withstand Wet
kV
85
76
88.4
Impulse Withstand Voltage (BIL)
kV
230
207
229.7
Impulse Flashover Positive
kV
238
221.5
241.3
Impulse Flashover Negative
kV
410
418.4
414.6
Weight
kg
15
16
18.5
Packed Weight
kg
15.5
16.5
19
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Colour
Packing Description (see Packing Pages)
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
5 - 01
LONG ROD INSULATORS
METALWARE:
Product Supplied with
Rivet Pin & Humpback
Split Pin
Clevis
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
Tongue
D
L
See Metalware Configuration
Socket
Ball
D
L
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP342-00 EP342-01 EP342-02 EP342-03 EP1125-00 EP1095-00
Nominal Voltage
kV
22
22
22
22
22
22
Connecting Length
L
mm
372
372
372
372
372
292
Largest Shed Dia.
D
mm
135
135
135
135
135
179
7
7
7
7
7
3(Big)
mm
585
585
585
585
585
610
Number of Sheds
Metalware
Configuration
Nominal Creepage Distance
Top Metalware Type
d1
mm
Clevis
Tongue
Clevis
Tongue
Clevis
Ball/Socket
Bottom Metalware Type
d
mm
Tongue
Tongue
Tongue
Clevis
Tongue
Ball/Socket
Metalware Position
d1
mm
In Line
In Line
Twisted
In Line
In Line
In Line
Tensile Strength
kN
40
40
40
40
70
40
Dry Arcing Distance
mm
230
230
230
230
230
227
Power Frequency Flashover Dry
kV
119
119
119
119
119
102.6
Power Frequency Flashover Wet
kV
62
62
62
62
62
53.7
Power Frequency Withstand Dry
kV
110
110
110
110
110
92.2
Power Frequency Withstand Wet
kV
50
50
50
50
50
49.1
Impulse Withstand Voltage (BIL)
kV
195
195
195
195
195
152.8
Impulse Flashover Positive
kV
198
198
198
198
198
159.8
Impulse Flashover Negative
kV
214
214
214
214
214
225.8
Weight
kg
6.7
6.7
6.7
6.7
6.7
---
Packed Weight
kg
7.5
7.5
7.5
7.5
7.5
---
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
5 - 02
LONG ROD INSULATORS
METALWARE:
Product Supplied with
Rivet Pin & Humpback
Split Pin
Clevis
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
Tongue
D
L
See Metalware Configuration
Socket
Ball
D
L
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP520-00 EP520-01 EP520-02 EP520-03 EP1116-00 EP933-00
Nominal Voltage
kV
22/33
22/33
22/33
22/33
22/33
22/33
Connecting Length
L
mm
438
438
438
438
438
450
Largest Shed Dia.
D
mm
135
135
135
135
135
130
9
9
9
9
9
8
mm
860
860
860
860
860
750
Number of Sheds
Metalware
Configuration
Nominal Creepage Distance
Top Metalware Type
d1
mm
Clevis
Tongue
Clevis
Tongue
Clevis
Clevis
Bottom Metalware Type
d
mm
Tongue
Tongue
Tongue
Clevis
Tongue
Tongue
Metalware Position
d1
mm
In Line
In Line
Twisted
In Line
In Line
In Line
Tensile Strength
kN
40
40
40
40
70
40
Dry Arcing Distance
mm
307
307
307
307
307
335
Power Frequency Flashover Dry
kV
125
125
125
125
125
153
Power Frequency Flashover Wet
kV
95
95
95
95
95
133
Power Frequency Withstand Dry
kV
120
120
120
120
120
140
Power Frequency Withstand Wet
kV
65
65
65
65
65
78
Impulse Withstand Voltage (BIL)
kV
210
210
210
210
210
230
Impulse Flashover Positive
kV
217
217
217
217
217
239
Impulse Flashover Negative
kV
258
258
258
258
258
285
Weight
kg
7.5
7.5
7.5
7.5
7.5
7
Packed Weight
kg
8.3
8.3
8.3
8.3
8.3
7.8
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
5 - 03
LONG ROD INSULATORS
METALWARE:
Product Supplied with
Rivet Pin & Humpback
Split Pin
Clevis
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
Tongue
D
L
See Metalware Configuration
Socket
Ball
D
L
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP933-01 EP933-02 EP933-03 EP1126-00 EP1044-00 EP1115-00
Nominal Voltage
kV
22/33
22/33
22/33
22/33
33
33
Connecting Length
L
mm
450
450
450
450
570
570
Largest Shed Dia.
D
mm
130
130
130
130
135
135
8
8
8
8
13
13
mm
750
750
750
750
1200
1200
Number of Sheds
Metalware
Configuration
Nominal Creepage Distance
Top Metalware Type
d1
mm
Tongue
Clevis
Tongue
Clevis
Clevis
Clevis
Bottom Metalware Type
d
mm
Tongue
Tongue
Clevis
Tongue
Tongue
Tongue
Metalware Position
d1
mm
In Line
Twisted
In Line
In Line
Twisted
Twisted
Tensile Strength
kN
40
40
40
70
40
70
Dry Arcing Distance
mm
335
335
335
335
430
430
Power Frequency Flashover Dry
kV
153
153
153
153
124
124
Power Frequency Flashover Wet
kV
133
133
133
133
97
97
Power Frequency Withstand Dry
kV
140
140
140
140
108
108
Power Frequency Withstand Wet
kV
78
78
78
78
78
78
Impulse Withstand Voltage (BIL)
kV
230
230
230
230
321
321
Impulse Flashover Positive
kV
239
239
239
239
333
333
Impulse Flashover Negative
kV
285
285
285
285
364
364
Weight
kg
7
7
7
7
8
8
Packed Weight
kg
78
7.8
7.8
7.8
8.8
8.8
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
5 - 04
LONG ROD INSULATORS
METALWARE:
Product Supplied with
Rivet Pin & Humpback
Split Pin
Clevis
Material: SG42/M.C.I
-To SABS 963/1970
-To BS 2789/1973-420/12
Hot Dip Galvanized
-To SABS 763
-To BS 729 or ISO 1461
Tongue
D
L
See Metalware Configuration
Socket
Ball
D
L
Tested to IEC 383/SABS 177:1990 Part III
Product No.
EP536-01 EP536-02 EP536-03 EP536-04 EP536-05 EP1124-00
Nominal Voltage
kV
66
66
66
66
66
66
Connecting Length
L
mm
840
840
840
840
819
840
Largest Shed Dia.
D
mm
160
160
160
160
160
160
18
18
18
18
18
18
mm
1800
1800
1800
1800
1800
1800
Clevis
Ball/Socket
Clevis
Number of Sheds
Metalware
Configuration
Nominal Creepage Distance
Top Metalware Type
d1
mm
Clevis
Clevis
Tongue
Bottom Metalware Type
d
mm
Clevis
Tongue
Tongue
Tongue Ball/Socket
Clevis
Metalware Position
d1
mm
In Line
In Line
In Line
Twisted
In Line
In Line
Tensile Strength
kN
70
70
70
70
70
120
Dry Arcing Distance
mm
662
662
662
662
662
662
Power Frequency Flashover Dry
kV
210
210
210
210
210
210
Power Frequency Flashover Wet
kV
160
160
160
160
160
160
Power Frequency Withstand Dry
kV
200
200
200
200
200
200
Power Frequency Withstand Wet
kV
150
150
150
150
150
150
Impulse Withstand Voltage (BIL)
kV
350
350
350
350
350
350
Impulse Flashover Positive
kV
360
360
360
360
360
360
Impulse Flashover Negative
kV
500
500
500
500
500
500
Weight
kg
21.8
21.8
21.8
21.8
21.8
21.8
Packed Weight
kg
23.7
23.7
23.7
23.7
23.7
23.7
Colour
Packing Description
Brown
Brown
Brown
Brown
Brown
Brown
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Wire Bound
Wood Crate
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
6 - 01
BUSSBAR SUPPORT INSULATORS
METALWARE:
MATERIAL: Various
Also customer supplied
Tested to IEC 383/SABS 177:1990 Part III
Product No.
Nominal Voltage
kV
Overall Length
A
mm
Porcelain Length
B
mm
Largest Shed Dia.
C
mm
Exposed Thread Length
D
mm
Top
mm
Bottom
Metalware
Description
Nominal Creepage Distance
Cantilever Strength
kN
Torsional Strength
Nm
Tensile Strength
kN
Compression Strength
kN
Dry Arcing Distance
mm
Power Frequency Flashover Dry
kV
Power Frequency Flashover Wet
kV
Power Frequency Withstand Dry
kV
Power Frequency Withstand Wet
kV
Impulse Withstand Voltage (BIL)
kV
Impulse Flashover Positive
kV
Impulse Flashover Negative
kV
Weight
kg
Packed Weight
kg
Colour
Packing Description
Subject to Technical Changes Without Notice
P O BOX 78
NOORDWYK
1687
TEL: 011 316 4584
FAX: 011 316 4586
022
SHACKLE INSULATOR
- TO S.A.B.S. 161
- VOLTAGES UP TO 1000V
`
Dimensions (mm)
Type No. EP No.
A
B
D
d
R
Dry
Wet
Withstand Withstand Puncture
Mechanical
Voltage
Voltage Voltage (kV) Strength (kN)
(kV)
(kV)
Packing
No. /
Box
Mass
(kg)
S. 03
EP8
57
63
35
11
5
17
8
25
6.25
100
23
S. 05
EP7
75
88
41
17
8
22
11
33
17.8
24
16
S. 1
EP6
88 100 57
18
13
26
14
39
17.8
24
20
S. 2
EP5
100 114 63
21
16
35
19
52
22.25
12
16
024
L.V. PIN INSULATOR
- WHITE GLAZED PORCELAIN
- TO S.A.B.S. 161
- VOLTAGES UP TO 1000V
Cordeaux
Thread
Dimensions (mm)
Dry
Wet
Withstand Withstand
Voltage
Voltage
DIA
(kV)
(kV)
(in)
Puncture
Voltage
(kV)
Mechanical
Strength
(kN)
Type
No.
EP No.
A
B
C
R1
R2
T.P.I.
P.03
EP12
75
63
35
4
5
7
1/2
30
15
45
P.05
EP11
88
75
41
5.5
5.5
6
5/8
34
17
P.1
EP10
100
88
50
7
8
6
5/8
40
P.2
EP9
120
100
53
11
11
6
3/4
50
Packing
No. /
Box
Mass
(kg)
2.7
48
16
51
2.7
24
13
20
60
2.7
24
18
22
74
2.7
12
21
IDENTIFICATION MARKINGS
The following transfers are typical on Cullin Africa insulators for identification - usually placed on
the top shed.
CIP Logo and South Africa
CIP Logo
Product code (EP965 F)
kV Rating (22kV)
Creepage distance (750mm)
Cantilever Strength (10kN)
Country of Manufacture (South Africa)
CIP Logo
Product code (EP1056)
kV Rating (132kV)
Creepage distance (4500mm)
Cantilever Strength (4kN)
IEC Designation (C4-650)
Country of Manufacture (South Africa)
South Africa
22kV
EP965 F
750mm Creep
10kN
South Africa
132kV
EP1056
4500mm Creep
4kN
C4-650
South Africa
Letter height: 3- 5mm
Cullin Africa will also mark insulators with customer's identification transfers as requested. Please
discuss your requirements with us.