Air cooled high temperature water chillers with screw

Transcription

Air cooled high temperature water chillers with screw
Air cooled high temperature water chillers
with screw compressors.
From 294 kW to 1.744 kW
FOCS-HT
Versions
Compressors/circuits
Cooling capacity (1)
EER (1)
Cooling capacity (2)
EER (2)
Maximum air temperature (operation at 100%) (3)
Maximum air temperature (part-load operation) (4)
ESEER
Sound power level (5)
Dimensions
kW
kW
°C
°C
dB(A)
mm
A
B
H
FOCS-HT
1502
1702
1902
1922
1972
2022
2602
2652
2702
2712
2722
3152
3602
B
B
B
B
B
B
B
B
B
2/2
294
2,91
250
2,06
50
57
3,86
98
2/2
328
2,73
270
1,84
50
57
3,75
98
2/2
364
2,72
307
1,91
50
57
3,74
99
2/2
414
2,81
361
1,92
50
57
3,85
99
2/2
439
2,80
383
1,89
50
57
3,84
99
2/2
480
3,01
424
2,05
50
57
3,88
99
2/2
529
2,87
446
1,97
50
57
3,76
99
2/2
562
2,89
476
1,97
50
57
3,88
99
2/2
598
2,87
509
1,96
50
57
3,98
99
2/2
625
2,88
543
1,97
50
57
3,89
101
2/2
681
3,08
603
2,10
50
57
4,07
101
2/2
730
2,80
627
1,80
50
57
3,94
101
2/2
785
2,71
678
1,89
50
57
3,94
101
B
B
B
4000
2260
2430
4000
2260
2430
4000
2260
2430
4900
2260
2430
4900
2260
2430
4900
2260
2430
4900
2260
2430
4900
2260
2430
4900
2260
2430
5800
2260
2430
5800
2260
2430
5800
2260
2430
5800
2260
2430
Versions
Compressors/circuits
Cooling capacity (1)
EER (1)
Cooling capacity (2)
EER (2)
Maximum air temperature (operation at 100%) (3)
Maximum air temperature (part-load operation) (4)
ESEER
Sound power level (5)
Dimensions
kW
kW
°C
°C
dB(A)
mm
A
B
H
3902
4202
4212
4222
4822
6002
6303
6903
7203
7213
7223
8404
B
B
B
B
B
B
B
B
B
2/2
831
2,76
702
1,88
50
57
3,78
102
2/2
900
2,80
757
1,86
50
57
3,79
102
2/2
968
2,75
835
2,03
50
57
3,78
103
2/2
1033
2,70
910
2,00
50
57
3,90
103
2/2
1157
3,01
1020
1,97
50
57
4,14
104
2/2
1242
2,88
1071
2,05
46
53
3,82
104
3/3
1336
2,85
1149
1,78
50
57
3,76
105
3/3
1433
2,77
1218
1,92
50
57
3,68
105
3/3
1486
2,79
1269
1,93
50
57
3,82
105
3/3
1570
2,84
1365
2,11
50
57
3,89
105
3/3
1609
2,72
1414
1,83
50
57
3,79
105
4/4
1744
2,73
1448
1,87
50
57
3,66
105
B
B
B
7000
2260
2430
7000
2260
2430
9400
2260
2430
9400
2260
2430
9400
2260
2430
9400
2260
2430
11200
2260
2430
11200
2260
2430
11200
2260
2430
11200
2260
2430
11200
2260
2430
11200
2260
2430
Note
(1) Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C
(2) Evaporator water (in/out) = 12/7°C; Condenser air (in) = 46°C
(3) Evaporator water (in/out) = 12/7°C
(4) Evaporator water (in/out) = 12/7°C; units partialized at 50%
(5) Sound power based on measurements taken in accordance with
standards ISO 3744 and Eurovent 8/1.
(*) data with economizer/s deactivated. To increase cooling capacity
enhancing the economizer operating limit, choose the oasis cooling
kit option or contact Climaveneta sales dpt.
Impact of Oasis on the condensation and operational limits
Relative Humidity outdoor air
[%]
30
40
50
60
70
Ambient air temperature, dry bulb
[°C]
Delta T inlet condenser coil
temperature [°C]
Water consumption for 1000m3/h
air flow [l/h]
35
40
45
35
40
45
35
40
45
35
40
45
35
40
45
6
6,5
7,5
5
5,5
6
4,5
5
5
3,5
4
4,5
3
4
4
5,1
5,6
6,1
4,0
4,6
5,2
3,3
3,7
4,1
2,3
2,6
2,8
1,4
1,6
1,7