Carrier Electronic Catalog 42 series selection program Version 2.0.4
Transcription
Carrier Electronic Catalog 42 series selection program Version 2.0.4
Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC004 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 1.97 1.56 27.0 / 50 7.0 4.0 0 426 0.426 9.6 2.13 1.80 27.0 / 50 7.0 4.3 0 426 0.426 9.6 2.48 2.33 27.0 / 50 7.0 5.0 0 426 0.426 9.6 l/s m3/h dBA dBA 100.0 360 30 21 125.0 450 37 28 183.3 660 47 38 mm mm mm 298 575 575 298 575 575 298 575 575 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 1/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office. Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC008 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 2.58 1.75 27.0 / 50 7.0 3.1 0 719 0.719 13.1 3.42 2.48 27.0 / 50 7.0 4.1 0 719 0.719 13.1 4.18 3.24 27.0 / 50 7.0 5.0 0 719 0.719 13.1 l/s m3/h dBA dBA 86.1 310 30 21 136.1 490 41 32 194.4 700 49 40 mm mm mm 298 575 575 298 575 575 298 575 575 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 2/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office. Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC010 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 3.58 2.51 27.0 / 50 7.0 3.6 0 847 0.847 22.1 4.12 3.01 27.0 / 50 7.0 4.2 0 847 0.847 22.1 4.93 3.86 27.0 / 50 7.0 5.0 0 847 0.847 22.1 l/s m3/h dBA dBA 130.6 470 43 34 166.7 600 48 39 236.1 850 54 45 mm mm mm 298 575 575 298 575 575 298 575 575 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 3/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office. Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC012 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 4.33 2.97 27.0 / 50 7.0 3.5 0 1058 1.06 18.3 5.22 3.73 27.0 / 50 7.0 4.2 0 1058 1.06 18.3 6.16 4.70 27.0 / 50 7.0 5.0 0 1058 1.06 18.3 l/s m3/h dBA dBA 152.8 550 34 25 194.4 700 40 31 305.6 1100 49 40 mm mm mm 298 825 825 298 825 825 298 825 825 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 4/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office. Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC016 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 5.00 3.26 27.0 / 50 7.0 2.9 0 1488 1.49 14.3 7.07 4.84 27.0 / 50 7.0 4.1 0 1488 1.49 14.3 8.66 6.23 27.0 / 50 7.0 5.0 0 1488 1.49 14.3 l/s m3/h dBA dBA 152.8 550 38 29 252.8 910 49 40 361.1 1300 56 47 mm mm mm 298 825 825 298 825 825 298 825 825 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 5/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office. Carrier Electronic Catalog 42 series selection program Version 2.0.4 Technical data and performance Unit reference 42GWC020 2 pipes, cooling only System type Fan speed Low Medium High kW kW °C / % °C °C % l/h m3/h kPa 5.98 3.90 27.0 / 50 7.0 2.6 0 1978 1.98 23.9 9.36 6.47 27.0 / 50 7.0 4.1 0 1978 1.98 23.9 11.51 8.41 27.0 / 50 7.0 5.0 0 1978 1.98 23.9 l/s m3/h dBA dBA 194.4 700 42 33 338.9 1220 55 46 486.1 1750 63 54 mm mm mm 298 825 825 298 825 825 298 825 825 Cooling mode Total capacity Sensible capacity Entering air (db / rh) Entering water temperature Water Delta T Glycol Water flow Water pressure drop Fan Air flow Sound power level Sound pressure level (*) Physical data Height Width Depth Options 2 pipe (*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains). 6/6 Important notice CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.