Carrier Electronic Catalog 42 series selection program Version 2.0.4

Transcription

Carrier Electronic Catalog 42 series selection program Version 2.0.4
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC004
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
1.97
1.56
27.0 / 50
7.0
4.0
0
426
0.426
9.6
2.13
1.80
27.0 / 50
7.0
4.3
0
426
0.426
9.6
2.48
2.33
27.0 / 50
7.0
5.0
0
426
0.426
9.6
l/s
m3/h
dBA
dBA
100.0
360
30
21
125.0
450
37
28
183.3
660
47
38
mm
mm
mm
298
575
575
298
575
575
298
575
575
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
1/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC008
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
2.58
1.75
27.0 / 50
7.0
3.1
0
719
0.719
13.1
3.42
2.48
27.0 / 50
7.0
4.1
0
719
0.719
13.1
4.18
3.24
27.0 / 50
7.0
5.0
0
719
0.719
13.1
l/s
m3/h
dBA
dBA
86.1
310
30
21
136.1
490
41
32
194.4
700
49
40
mm
mm
mm
298
575
575
298
575
575
298
575
575
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
2/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC010
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
3.58
2.51
27.0 / 50
7.0
3.6
0
847
0.847
22.1
4.12
3.01
27.0 / 50
7.0
4.2
0
847
0.847
22.1
4.93
3.86
27.0 / 50
7.0
5.0
0
847
0.847
22.1
l/s
m3/h
dBA
dBA
130.6
470
43
34
166.7
600
48
39
236.1
850
54
45
mm
mm
mm
298
575
575
298
575
575
298
575
575
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
3/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC012
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
4.33
2.97
27.0 / 50
7.0
3.5
0
1058
1.06
18.3
5.22
3.73
27.0 / 50
7.0
4.2
0
1058
1.06
18.3
6.16
4.70
27.0 / 50
7.0
5.0
0
1058
1.06
18.3
l/s
m3/h
dBA
dBA
152.8
550
34
25
194.4
700
40
31
305.6
1100
49
40
mm
mm
mm
298
825
825
298
825
825
298
825
825
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
4/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC016
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
5.00
3.26
27.0 / 50
7.0
2.9
0
1488
1.49
14.3
7.07
4.84
27.0 / 50
7.0
4.1
0
1488
1.49
14.3
8.66
6.23
27.0 / 50
7.0
5.0
0
1488
1.49
14.3
l/s
m3/h
dBA
dBA
152.8
550
38
29
252.8
910
49
40
361.1
1300
56
47
mm
mm
mm
298
825
825
298
825
825
298
825
825
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
5/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.
Carrier Electronic Catalog
42 series selection program
Version 2.0.4
Technical data and performance
Unit reference
42GWC020
2 pipes, cooling only
System type
Fan speed
Low
Medium
High
kW
kW
°C / %
°C
°C
%
l/h
m3/h
kPa
5.98
3.90
27.0 / 50
7.0
2.6
0
1978
1.98
23.9
9.36
6.47
27.0 / 50
7.0
4.1
0
1978
1.98
23.9
11.51
8.41
27.0 / 50
7.0
5.0
0
1978
1.98
23.9
l/s
m3/h
dBA
dBA
194.4
700
42
33
338.9
1220
55
46
486.1
1750
63
54
mm
mm
mm
298
825
825
298
825
825
298
825
825
Cooling mode
Total capacity
Sensible capacity
Entering air (db / rh)
Entering water temperature
Water Delta T
Glycol
Water flow
Water pressure drop
Fan
Air flow
Sound power level
Sound pressure level (*)
Physical data
Height
Width
Depth
Options
2 pipe
(*) : Sound Pressure Levels are measured in a room of 100 m3 volume and 0.5 sec reverbation time (e.g. living room with wall-to-wall carpet and curtains).
6/6
Important notice
CAUTION: The manufacturer reserves the right to modify the products at any time and without prior notice. Please confirm all selections at time of order with your local Carrier office.