SmartPro 120V 700VA 450W Line-Interactive UPS

Transcription

SmartPro 120V 700VA 450W Line-Interactive UPS
SmartPro 120V 700VA 450W Line-Interactive UPS,
Tower, DB9 Serial
NUMÉRO DE MODÈLE: SMART700SER
Points principaux
700VA line interactive tower UPS
system
120V nominal output during
brownouts to 75V and
overvoltages to 147V
Front panel status LEDs with
load and battery capacity level
display
RS232 communications port;
Hot-swappable batteries
NEMA 5-15P input; 6 NEMA
5-15R outlets
Inclut dans l'emballage
SMART700SER UPS System
Serial cable
Instruction manual
Présentation générale
Tripp Lite's SMART700SER is an intelligent, line-interactive UPS with DB9 serial port. It protects servers, networking accessories and telecommunications
equipment from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 16.9 minutes half load runtime and 5.9 minutes at full load
during power failures. 700VA/450 watt power handling capability supports a variety of networking, telecom and various other application types, including the
support of multiple network workstations. Includes a total of 6 UPS supported outlets. Supports remote monitoring of UPS and site power conditions via built-in
DB9 serial port. PowerAlert UPS monitoring and unattended shutdown software is available for free download. Built-in audible alarm and 5 front panel LEDs
indicate status of line power, battery power, battery low/replace, voltage regulation and load level. Wall mountable with user-supplied UPSWM wall-mount
bracket. Network-grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges. Attractive,
small-footprint tower housing uses minimal floor or desktop space.
Fonctionnalités
700VA/450 watt power handling capability supports a variety of networking, telecom and various other application types
Built-in voltage regulation and battery support, plus complete AC modem line surge suppression prevents equipment damage, data loss and downtime
Large internal batteries offer 16.9 minutes half load runtime and 5.9 minutes at full load during power failures
Intelligent battery management system extends battery life
Automatic Voltage Regulation (AVR) circuits with two boost and one voltage reduction level maintains usable 120V nominal output over an input voltage
range of 75-147V
Includes a total of 6 NEMA5-15R outlets
Communications ports support timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected equipment
Serial port enables data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from
www.tripplite.com/poweralert
Battery replacement door
Notification of system status via 5 LEDs and multi-function audible alarms
Wall mountable with user-supplied UPSWM wallmount bracket
Cold start capability enables UPS turn-on in battery mode during blackout conditions
1/5
Caractéristiques
Sortie
Puissance en volts-ampères (VA)
700
Capacité en sortie (Watts)
450
Tension(s) de sortie nominale(s)
prise(s) en charge
110 V; 115 V; 120 V
Détails de la tension nominale
115v nominal output in battery mode
Compatibilité avec fréquences
60 Hz
Régulation de la tension de sortie
(mode ligne)
-18%, +8%
Régulation de la tension de sortie
(mode batterie)
+/- 5%
Prises de sortie
(6) 5-15R
Forme d'onde CA de sortie (mode
CA)
Sine wave
Forme d'onde de sortie CA (mode
Batterie)
Signal sinusoïdal à modulation d'impulsions en largeur
Entrée
Courant d'entrée nominal (charge
maximale)
4.33A
Tension(s) d'entrée nominale(s)
prise(s) en charge
120 V CA
Type de connexion d'entrée de
l'onduleur (UPS)
5-15P
Disjoncteurs de circuit d'entrée
10A
Longueur du cordon d'entrée de
l'onduleur (pi)
7
Longueur du cordon d'entrée de
l'onduleur (m)
2.1
Service électrique recommandé
15A 120V
Phase en entrée
Monophasé
Batterie
Durée de fonctionnement à pleine
charge (min.)
5.9 min. (450w)
Durée de fonctionnement à
demi-charge (min.)
16.9 min. (225w)
Tension du système CC (V CC)
12
Taux de recharge des batteries
(Batteries incluses)
Less than 6 hours from 10% to 90% (typical, full load discharge)
2/5
Cartouche de batterie de rechange
de l'onduleur interne
RBC52(x2)
Accès aux batteries
Battery access door
Description du remplacement de la
batterie
Hot-swappable, user replaceable batteries
Autonomie extensible
Non
Régulation de tension
Description de la régulation de
tension
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Correction des surtensions
Input voltages between 128 and 147 are reduced by 12%
Correction des sous-tensions
Input voltages between 93 and 107 are boosted by 14%
Correction des fortes sous-tensions
Input voltages between 75 and 92 are boosted by 30%
Interface Utilisateur, Alarmes et Contrôles
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
Fonctionnement de l'annulation
d'alarme
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Alarme sonore
Audible alarm indicates power-failure and low-battery conditions
Indicateurs LED
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Suppression de Bruit / Surtensions
Coefficient de suppression Joules
CA onduleur
480
Temps de réponse suppression CA
onduleur
Instantaneous
Suppression de bruit CA RFI / IEM
Oui
Physiques
Facteurs de forme d'installation pris
en charge avec accessoires
optionnels
Montage mural (UPSWM - kit de montage en tour)
Facteur de forme primaire
Tour
Dimensions du module
d'alimentation de l'onduleur (hlp, po)
11.8 x 7.2 x 7.8
Dimensions du module
d'alimentation de l'onduleur (hlp, cm)
29.8 x 18.4 x 19.7
Poids du module d'alimentation de
l'onduleur (livres)
21
Poids du module d'alimentation de
l'onduleur (kg)
9.53
Dimensions d'expédition de
l'onduleur (hlp / po)
15 x 11.2 x 10.8
3/5
Dimensions d'expédition de
l'onduleur (hlp / cm)
38.1 x 28.6 x 27.3
Poids d'expédition (livres)
23.5
Poids d'expédition (kg)
10.7
Matériau du boîtier de l'onduleur
Polycarbonate
Hauteur de l'onduleur principal (mm)
300
Largeur de l'onduleur principal (mm)
183
Profondeur de l'onduleur principal
(mm)
198
Hauteur d'expédition (mm)
381
Largeur d'expédition (mm)
284
Profondeur d'expédition (mm)
274
Ecologique
Plage de température de
fonctionnement
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Plage de température de stockage
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Humidité relative
0 to 95%, non-condensing
BTU mode CA / Hr. (pleine charge)
98
BTU mode batterie / Hr. (pleine
charge)
384
Coefficient de rendement mode CA
(Charge 100 %)
92%
Communication
Interface de communication
Série DB9
Description du port de surveillance
réseau
Supports detailed monitoring of UPS and site power conditions
Logiciel PowerAlert
For local monitoring via the UPS’s built-in serial port, download PowerAlert Local software at
http://www.tripplite.com/poweralert
Câble de communications
DB9 serial cable included
Transfert Ligne / Batterie
Temps de transfert
2-4 milliseconds
Transfert basse tension vers
alimentation batterie (Consigne)
75
Transfert haute tension vers
alimentation batterie (Consigne)
147
Fonctions spéciales
4/5
Démarrage à froid (Démarrage en
mode batterie pendant une coupure
de courant)
Cold-start operation supported
Fonctions de haute disponibilité de
l'onduleur
Batteries remplaçables à chaud
Certifications
Certifications onduleur
Testé selon la norme UL1778 (États-Unis); Testé selon les normes CSA (Canada); Certifié FCC Part 15 Category A
(EMI)
Garantie
Période de garantie du produit
(Mondiale)
Garantie de 2 ans
Assurance équipements connectés
(États-Unis, Canada et Porto Rico)
$250,000 Ultimate Lifetime Insurance
© 2016 Tripp Lite. Tous les droits sont réservés. Tous les noms de produits et de sociétés sont des marques commerciales ou des marques déposées de leurs
détenteurs respectifs. Leur utilisation ne comporte aucune affiliation avec ou approbation par eux. Tripp Lite a une politique d'amélioration continue. Les
spécifications sont sujettes à modification sans préavis. Tripp Lite utilise les agences primaires et de tiers pour tester ses produits pour conformité aux normes.
Voir la liste des agences d’essais de Tripp Lite:
5/5