TKL 2x4 Installation Instructions - Precision

Transcription

TKL 2x4 Installation Instructions - Precision
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
Product Information
Project Name
Type
Catalog Number
Date
INCLUDED MATERIALS
A. (1) 2x4 TKL Retrofit Assembly
B. (2) Tab Bracket (p/n 95001747-M069)
C. (6) #8-18 x 1/2” Self-Drilling Sheet Metal Screw
p/n 95000989 SCR 8-18X1/2 HWH SD2 ZN
MATERIALS REQUIRED
•
Wiring Nuts of Appropriate Size and Quantity
TOOLS REQUIRED
•
•
•
•
•
Electric driver drill, standard jaw chuck
1/4” hex nutdriver bit
Electric wire cutter / stripper
Screwdrivers, Phillips and slotted
Personal safety equipment
ENGLISH - WARNINGS & SAFETY INFORMATION:
PLEASE READ CAREFULLY!
•
•
•
•
•
•
•
•
WARNING - Risk of fire or electric shock. Luminaire
wiring and electrical parts may be damaged
when drilling for installation of LED retrofit kit.
Check for enclosed wiring and components.
WARNING - Risk of fire or electric shock. LED Retrofit
Kit installation requires knowledge of luminaires
electrical systems. If not qualified, do not attempt
installation. Contact a qualified electrician.
WARNING - Risk of fire or electric shock. Install this kit only
in the luminaires that have the construction features and
dimensions shown in the photographs and/or drawings.
Only those open holes indicated in the photographs
and/or drawings may be made or altered as a result of
kit installation. Do not leave any other open holes in
an enclosure of wiring or electrical components.
WARNING - To prevent wiring damage or abrasion, do not
expose wiring to edges of sheet metal or other sharp objects.
WARNING - This product is sensitive to Electrical
Static Discharge (ESD). Care should be taken to avoid
direct contact with the LEDs. Installers should be
grounded using a wrist strap or other suitable method
of grounding. Failure to ground the installer may cause
pre-mature failures and void the fixture warranty.
Fixture is suitable for damp locations.
THE RETROFIT KIT IS ACCEPTED AS A COMPONENT
OF A LUMINAIRE WHERE THE SUITABILITY OF THE
COMBINATION SHALL BE DETERMINED BY CSA
OR AUTHORITIES HAVING JURISDICTION.
FRANÇAIS - MISES EN GARDE ET SÉCURITÉ:
SE IL VOUS PLAÎT LIRE ATTENTIVEMENT!
•
•
•
•
•
•
•
•
AVERTISSEMENT - Risque d'incendie ou de choc
électrique. Câblage du luminaire et pièces électriques
peuvent être endommagés lors du perçage pour
l'installation du kit de conversion à DEL. Vérifier
le câblage et les composants intérieur.
AVERTISSEMENT - Risque d'incendie ou de choc électrique.
Installation du Kit d'adaptation DEL nécessite la connaissance
des systèmes électriques des luminaires. Si non qualifié, ne
essayez pas l'installation. Contactez un électricien qualifié.
AVERTISSEMENT - Risque d'incendie ou de choc
électrique. Installez ce kit dans les luminaires qui ont
les caractéristiques de construction et dimensions
indiquées dans les photographies et/ou dessins.
Seuls les trous ouverts indiqués dans les photographies et/
ou dessins peuvent être effectués ou modifiés à la suite de
l'installation du kit. Ne laissez pas d'autres trous ouverts dans
un ensemble de câblage ou de composants électriques.
AVERTISSEMENT - Pour éviter d'endommager le
câblage ou l'abrasion, ne pas exposer le câblage
aux bords ou d'autres objets pointus.
AVERTISSEMENT - Ce produit est sensible aux décharges
d'électricité statique (ES). Des précautions doivent être prises
pour éviter le contact direct avec les DEL. Les installateurs
doivent être mis à la terre en utilisant un bracelet ou une autre
méthode appropriée de mise à la terre. Defaut de mécanisme
à la terre le programme d'installation peut provoquer des
défaillances prématurées et annuler la garantie du luminaire.
Luminaire est adapté aux endroits humides.
LE KIT DE MODIFICATION EST ACCEPTÉ COMME UNE
COMPOSANTE D'UN LUMINAIRE OÙ LA PERTINENCE
DE LA COMBINAISON DOIT ÊTRE DÉTERMINÉE PAR
LA CSA OU LES AUTORITÉS AYANT JURIDICTION.
Page 1/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon [P2] reserves the right to change
specifications without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
INSTALLATION INSTRUCTIONS
1. To avoid the possibility of electric shock, turn off power.
2. Open the troffer and remove existing lamps, lamp mounts,
ballasts / drivers, interconnection components, etc. (Fig. 1)
Fig. 1
3. Using the #8 self-drilling sheet metal screws, install
the 2 Tab Brackets in the center of each short side of
the troffer, against the troffer’s end caps (Figs. 2, 3, 4).
Fig. 2
The Tab Brackets should be positioned up against
the opposite ends of the troffer, and centered
to within +/- 1/8” of the troffer’s centerline.
Fig. 3
4. (View looking upward into the troffer, after the
Tab Brackets have been installed - Fig. 4)
Fig. 4
Page 2/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon reserves the right to change specifications
without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
INSTALLATION INSTRUCTIONS
5. Bring the TKL Retrofit
Assembly up to the troffer.
Locate the safety cables at
each end of the Retrofit
Assembly (Fig. 5).
Safety Cables
Fig. 5
6. Using 2 of the self-drilling sheet metal screws, secure the
safety cables to the troffer body (Figures 6 and 7):
Fig. 6
Fig. 7
Page 3/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon reserves the right to change specifications
without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
INSTALLATION INSTRUCTIONS
7. Fasten the service cable’s ground wire to the ground
lead of the TKL Retrofit Assembly (Figure 8).
8. Connect the input service cable’s voltage
supply wires to the TKL Retrofit Assembly.
TKL ground lead
Fig. 8
9. Lift the TKL Retrofit Assembly up
into the troffer enclosure (Fig 9).
10.To secure the TKL Retrofit Assembly to the Tab Brackets,
engage the Retrofit Assembly’s slots into the Tab Bracket’s
tabs one side at the time, as shown in Figures 10 and 11.
Fig. 9
Fig. 10
Slide the Retrofit Assembly sideways, such
that one of its slots engages their tabs, as shown.
Page 4/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon reserves the right to change specifications
without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
INSTALLATION INSTRUCTIONS
10.Continued from previous page.
Then, pinch together the Gear Tray’s
central channel, such that the other
set of slots can engage their tabs.
Fig. 11
11.Connect the leads which are labeled
“Emergency Battery.” This will connect
the emergency battery, causing the
LEDs to turn on (even though line
power has not yet been energized).
12.Close and secure the lens door (Fig. 12).
13.Carefully check all mechanical
and electrical connections.
14.Installation Complete. Apply power to the fixture.
Fig. 12
Page 5/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon reserves the right to change specifications
without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com
13.81"
2.07"
TKL
LED Prismatic Troffer Conversion Kit
2x4 Installation Instructions
23.00" Minimum Required Opening in Existing Fixture
MINIMUM DIMENSIONS OF EXISTING FIXTURE OPENING
2X4 TKL CROSS SECTION & SIDE VIEW
13.81"
2.08"
46.69" Minimum Required Opening in Existing Fixture
*Drawings N.T.S.
FIT AND FUNCTION
Minimum dimensional requirements are above but Precision-Paragon[P2] recommends
a trial installation prior to ordering project quantities. TKL Coversion Kits are designed
to fit into most lensed-recessed prismatic troffers mounted in T-grid installation.
Page 6/6 - Revised 03/25/15
© 2015 Precision-Paragon [P2], a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Precision-Paragon reserves the right to change specifications
without notice. Tel [West Coast] 714.386.5550 [Midwest] 715.381.2971 [East Coast] 352.692.5900 / Website www.P-2.com